Home Product Product Quality Manager

Product Quality Manager

이미지명
이미지명
  • Data Gather

Analog Channel Input •  Max. 64 Channels(Voltage, Current, Variable DC)
 • Voltage(rating : 63.5/110V/190V/240V)
 • Measurable range
- Voltage : 0.1V ~ 150V(±0.5%), 150V~(±1.0%)
- Current : 0.06A~50A(±1.0%), 50.0A~(±1.0%)
      - Current(Rating : 5A or 1A)
      - Input Charge : below 1VA
 
◈ Particular Data ◈    
      - (DC Voltage : 4  ~ 20mA)
      - (DC Current : -10V ~ +10V)
Digital Channel Input •  Max. 128 Channels(Variable)    
      - Dry Contact(DC 24V)
- Wet Contact(DC 45V, 90V, 125V)
      - Input Charge : below 1VA
Digital Output Channel •  Total 4 Channels
•  Triger occur
•  Printer Error
•  Communication Error
•  System Error
•  Relay Output (Select A / B Contact)
      - 120 VAC, 0.6A
      - 110 VDC, 0.6A
      - 30 VDC, 2.0A
 
Data Sampling •  Sampling Frequency : 7,680Hz (128 Sampling/Cycle)
•  A/D Resolution : 20 Bit(16 Bit AD + 4Bit) (Switching method)   
                          •  Sampling Method : Simultaneous Sampling for all Channels
  • Communication

Communication Method RS-232C/Ethernet(TCP/IP)
Digital Channel Input •  Max. 128 Channels(Variable) 
          - Dry Contact(DC 24V)
- Wet Contact(DC 45V, 90V, 125V)
      - Input Charge : below 1VA
Communication Device Ethernet Card, Hub
  • Trigger Element for Measuring Object

Saving Elements •  Trigger Data file(Extension : *.trg)
   - Instantaneous value of each sample for AI 64, DI variable channel
(Save max. 1 second before and 10 seconds after fault)
•  Phasor Data file(Extension : *.pha)
   - Phasor value of 1 time/cycle for AI 64
      (Save max. before 10 sec and after 1,200sec of fault)
•  Logging Data(Extension : *.RDI)
   - Logging up to max. 32 selected data (PQVf, Channel phasor) by user.
   - Saving cycle : Min.1 Second, possible to setup time by user option.
   - Saving Method : Continuous saving(from present time) 
                              1 time saving(within specific time)
                               Repeated saving (for specific section)
   -  When the saving time has over One day considering volume of file,
save Logging data to present time and produce new file for saving.
  • Saving Element and Saving Medium

Measuring Object P, Q, V, f, I, θ(phase), PF
Trigger Elements •  By each Channel  
- Level Trigger
 - ROC Trigger
•  By each Feeder     - P, Q Level Trigger
- P, Q ROC Trigger
 - P, Q Swing Trigger
•  By Each Trigger
- Level Trigger 
- ROC(Rate Of Change) Trigger
•  Manual Trigger
•  External Trigger
•  Remote Trigger
•  Event Trigger
top